8/6/2023 0 Comments Ups apc charge led error code(And actually, I have not seen this nearly so much on the SURT/SURTA series that you have. Luckily I think the 5th-generation units have improved some of these things. You can fix this (as well as another common problem of excessive float-charge voltage that prematurely kills batteries) if you have the right information, but APC won't give that out any more. (Which is worse than having no UPS installed at all.) And it's particularly pernicious because it will appear that everything is fine, until you have a short power-interruption, whereupon the battery may just immediately drop the load, depending on settings. This is a very common problem with SmartUPS 3rd-gen/4th-gen units: downgrading their runtime calibration due to old/bad batteries, and then not properly adjusting when a new set of batteries is installed, even after a runtime calibration attempt. Load Battery Charge Online The online LED illuminates when the UPS is supplying utility power to the con-nected equipment. The fact that the battery LEDs show 100% and the runtime in the management card or software app shows a reasonable amount does not guarantee the problem is fixed. This was originally posted on APC forums on